Wire Size Calculator (Ampacity, 125% Rule and Voltage Drop)

What gauge wire you need for a circuit: copper or aluminum size from the NEC ampacity table at the right temperature column, with the 125% continuous-load rule, the small-conductor breaker limits and an optional voltage-drop check for long runs.

Formula

Design amps = load × 1.25 if continuous. Size = smallest AWG whose ampacity in the 60 °C (or 75 °C) column, capped by 240.4(D) for 14/12/10 AWG, is at least the design amps. Voltage drop % = 2 × K × I × L ÷ cmil ÷ V × 100 (√3 for three phase; K = 12.9 copper, 21.2 aluminum); step up until within the limit.

Worked example

Inputs: Load current = 24 A; Continuous load (3 hours or more)? = Yes (size at 125%); Conductor = Copper; Wire type = THHN/THWN-2 or similar in conduit; Breaker/terminal rating = 60 °C (default for 100 A or less); Circuit voltage = 240 V; Phase = Single phase; One-way length (0 = skip voltage drop) = 100 ft; Maximum voltage drop = 3 %.

Design amps30
Ampacity column c60
Size by ampacity awg10
Ampacity used a30
Voltage drop pct at that size2.49
Recommended size awg10
Voltage drop pct at recommended2.49
Max breaker small conductor rule30 A (NEC 240.4(D))

Continuous loads (3 h or more) are sized at 125%. Circuits of 100 A or less, or 14–1 AWG, use the 60 °C column unless the equipment is listed for 75 °C (NEC 110.14(C)); NM cable always uses 60 °C. 240.4(D) caps the breaker on 14, 12 and 10 AWG. No ambient-temperature or bundling corrections are applied. Voltage drop uses the same K-factor method as our voltage-drop calculator.

FAQ

What size wire for 20 amps?

12 AWG copper: 20 A in the 60 °C column, and 240.4(D) limits 12 AWG copper to a 20 A breaker. 14 AWG is limited to 15 A.

What size wire for 30, 40 and 50 amps?

Copper at 60 °C: 30 A needs 10 AWG, 40 A needs 8 AWG and 50 A needs 6 AWG (55 A). 8 AWG (50 A) works for 50 A only where the 75 °C column applies, and never for NM cable.

What is the 125% rule?

Loads that run 3 hours or more are continuous; size the conductor and breaker for 125% of them. A 24 A continuous load needs 30 A of ampacity, so 10 AWG copper.

When do I need bigger wire for distance?

When voltage drop gets too high. A 40 A load at 240 V, 150 ft one way: 8 AWG copper drops 3.9%, 6 AWG drops 2.5%. Many designers aim for 3% on a branch circuit.

Can I use the 90 °C column for THHN?

Only as the starting point for temperature and bundling corrections. The final ampacity is limited by the terminal rating, usually 60 °C or 75 °C (NEC 110.14(C)). This calculator does not apply corrections, so check with your inspector or an electrician.